A complete ballistic lining for live-fire rooms: fixed and movable walls, ceiling, floor, acoustics and viewing glass. Each system is specified to work with the others, so rounds are held, fragments are collected and noise stays within limits.

Kill house section drawing Indicative cross-section of a live-fire room: fixed ballistic panels on the RCC walls, a movable dual-sided modular wall on locking wheels, a two-layer ceiling lining, rubber floor panels, acoustic panels in the observation corridor and a ballistic glazing window between room and corridor. Live-fire roomObservation corridorExisting truss / RCC 03 01 04 02 05 06 25 mm fragment gap
Hover a system to locate itIndicative section, not to scale
  1. 01Fixed wall panels130 mm rubber–steel composite
  2. 02Modular wall systems250 mm, dual-sided, on locking wheels
  3. 03Ceiling systemsBallistic base lining + acoustic layer
  4. 04Floor panels50 mm hot-moulded crumb rubber
  5. 05Acoustic insulationTarget ≤ 80 dB during live fire
  6. 06Ballistic glazing40 mm, EN 1063 BR6 / NIJ Level III
// Why a system

Four hazards, one lining

Live fire indoors creates four problems at once. No single panel solves all of them, which is why the room is specified system by system.

Ricochet

Walls and modular partitions face the room with 50 mm of hot-moulded rubber over a steel backing, designed to hold a round in the panel instead of returning it into the room.

Systems 01, 02, 04

Fragments

Wall panels stop 25 mm short of the floor. That gap collects fragments and is covered with an anti-ricochet rubber barrier; the crumb-rubber floor captures the rest.

Systems 01, 02, 04

Noise

Acoustic wall panels and a 100 mm rubber-wood ceiling composite target an internal sound level of 80 dB or less during 7.62 mm and 5.56 mm live fire.

Systems 03, 05

Observation

Viewing windows use 40 mm borosilicate and polycarbonate glazing rated EN 1063 BR6 / NIJ Level III, set in powder-coated MS frames.

System 06
// Technical specification

Specification by system

Supply and installation requirements for each ballistic-resistant facility component. Panel modules are 500 × 500 mm unless stated.

Every section strip below is drawn on the same millimetre scale, so thicknesses compare directly.

System 01

Fixed wall
panels

500 × 500 × 130 mm

Composite rubber and steel lining for the room's existing RCC walls, designed to stop bullet ricochet and fragmentation at the strike face.

Rubber layer
50 mmShredded, hot-moulded, bonded rubber
Laminated wood
18 mmLaminated wood layer
Air vent structure
50 mmMS tubular structure for ventilation
Steel backing
10 mmHigh-carbon steel plate, 450 HBW hardness
Protective coating
1–2 mmPyrite-based protective coating
Tolerance
±5 mm

Installation

  • Anchored to existing RCC walls using MS-framed structural supports
  • Chemical resin-based anchor rods: M16 × 190 mm, galvanised grade 5.8 bolts
  • 25 mm gap kept between floor and the panel's bottom edge for bullet fragment collection
  • Floor gap covered with anti-ricochet rubber barriers

PerformanceComplies with ballistic evaluation standards for close-combat training environments.

System 02

Modular wall
systems

500 × 500 × 250 mm

Movable close-combat panels with protection on both faces, so the room can be reconfigured for each drill without losing ballistic cover.

Overall thickness
250–300 mm±10 mm tolerance
Rubber layers
50 mm, both sidesShredded, hot-moulded rubber
Wood layers
18 mm, both sidesLaminated wood
Air vent structure
50 mm, both sidesMS tubular
Steel backing
10 mmHigh-carbon steel plate, 450 HBW
Mobility
Heavy-duty locking wheelsAnchored to MS frame

Installation

  • Mounted on an MS-framed base structure with adjustable locking wheels
  • 25 mm clearance kept above the floor for fragment collection
  • Configured on site to match training requirements
System 03

Ceiling
systems

95 mm + 100 mm linings

Two linings work together overhead: a ballistic base layer anchored to the truss, and a rubber-wood composite above it for noise and vibration.

3.1 Ballistic resistant base lining 500 × 500 × 95 mm

MS layer
6 mmMild steel
Air void
50 mmVentilation space
Wooden support
36 mmWooden stopper, braced with polyethylene

Installation

  • Anchored to the existing truss structure using M12 galvanised bolts

3.2 Acoustic ceiling composite lining 500 × 500 × 100 mm

Material
Hot-moulded rubber-wood fibre compositeRubberwood™ brand or equivalent
Composition
Crumb rubber granulesBonded with 1 mm width cement composite
Thickness
100 mm

Installation

  • Installed above the wooden stoppers for vibration isolation and acoustic management
System 04

Floor ballistic
panels

500 × 500 × 50 mm

Shock-absorbing floor protection that captures bullet fragments and reduces ricochet off the floor.

Material
Crumb rubber granulesPolymerically bonded
Manufacturing
Hot-moulded cured technology
Thickness
50 mm
Purpose
Capture fragments, reduce ricochet
System 05

Acoustic
insulation

Minimum 50 mm

Noise-reduction panels on the interior perimeter walls, sized to keep sound inside the facility within limits during live fire.

Location
All interior perimeter wallsRoom- and corridor-facing surfaces
Performance target
≤ 80 dB internal sound levelDuring live fire
Ammunition classes
7.62 mm and 5.56 mm calibres
Mounting
Secured to framed support structure
System 06

Ballistic-resistant
glazing

Minimum 40 mm

Viewing windows between the live-fire room and the observation side, rated against rifle and pistol rounds.

Glass type
Borosilicate glassWith polycarbonate interlayers
Standard
EN 1063 Class BR6 / NIJ Level III
Ballistic rating
Defeats 7.62 × 51 mm NATO, 9 mm Parabellum, 5.56 × 45 mmAt rated test distances
Frame
Heavy-duty MS hollow section75 × 50 × 4 mm, powder-coated
Anchoring
M16 chemical anchorsMinimum 4 per vertical section, top and base
Sealing
Structural silicone sealantAt all glass-to-frame joints
// General requirements

From sample to sign-off

Every installation follows the same sequence, with testing before bulk work and inspection after it.

  1. Site specification

    Layout, anchoring and fixings are set against site-specific requirements and the engineer's specification.

  2. Sample testing

    Quality assurance testing on representative samples before any bulk installation begins.

  3. Installation

    All fixings and anchors are certified for load-bearing and ballistic applications.

  4. Inspection

    Mandatory post-installation inspection verifies structural integrity and ballistic protection.

All materials must conform to the stated ballistic evaluation standards.